The suite must be separated by a fire separation having not less than a 45 minute fire resistance rating, Division B, Sentence 9.10.9.14. Separation of Residential Suites (1) Except as provided in Sentences (2) and (3) and Article 9.10.20.2., suites in residential occupancies shall be separated from adjacent rooms and suites by a fire separation having a fire-resistance rating of not less than 45 min.
(1) Except as provided in Sentences (2) and (3) and Article 9.10.21.2., suites in residential occupancies shall be separated from adjacent rooms and suites by a fire separation having a fire-resistance rating of not less than 45 min.
(2) Sleeping rooms in boarding, lodging or rooming houses where sleeping accommodation is provided for not more than 8 boarders or lodgers shall be separated from the remainder of the floor area by a fire separation having a fire-resistance rating of not less than 30 min where the sleeping rooms form part of the proprietor's residence and do not contain cooking facilities.
(3) Dwelling units that contain 2 or more storeys including basements shall be separated from the remainder of the building by a fire separation having a fire-resistance rating of not less than 1 h.
If the house was built before 2010, the fire separation ratings for floors can be reduced to 15 minutes; where the existing ceiling is finished with drywall and the smoke alarms are interconnected and hardwired to the other smoke alarms in the building. The fire separation rating for the walls can be reduced to 30 minutes, where the walls are existing; (new walls will require 45 min protection; type X drywall)
Houses built after 2010 require separate heating facilities for each suite. In houses constructed before 2010, where the furnace will be shared; a duct-type smoke detector must be located in the supply or return air plenum, which is triggered to shut off the furnace when smoke is present.
